Summary

"The air con isn't cooling" is one of the vaguest fault descriptions a tradesperson hears, covering everything from a five-minute filter clean to a compressor failure needing a full replacement. A systematic decision tree stops engineers (and homeowners on the phone) jumping straight to "it needs re-gassing" — the most expensive assumption, and usually the wrong one. A genuine refrigerant leak is a real and common cause of poor cooling, but it typically sits behind several cheaper, faster, legally unrestricted checks.

This matters to general AC and refrigeration engineers, electricians and plumbers who increasingly fit and service domestic split systems, and anyone fielding a call-out where the customer has already decided (usually wrongly) what's broken. It also matters because of the legal boundary running through the middle of this fault tree: anyone can check a filter, clear a condensate line, or investigate a thermostat setting, but only an F-Gas certified engineer may connect gauges to the refrigerant circuit, recover refrigerant, or add charge.

The most common misconception is that "not cooling" always means "needs refrigerant." In reality, airflow restriction (a dirty filter or fouled outdoor coil) and condensate-related safety lockouts account for a large share of domestic call-outs, resolved without ever touching the sealed circuit. Work the cheap checks first — it's faster for the customer and the only way to know whether refrigerant work is genuinely needed before booking a certified engineer's time.

Key Facts

Quick Reference Table

Diagnosed the problem? Create a repair quote in minutes with squote.

Try squote free →
Symptom Likely Cause Who Can Fix It
Weak airflow, mild cooling Blocked filter Customer or any engineer
No cooling, fan runs, outdoor unit iced/dirty Fouled condenser coil, restricted airflow Any engineer (no refrigerant access)
System shuts off completely, water near indoor unit Blocked condensate drain / failed condensate pump Any engineer (no refrigerant access)
Runs but room never reaches setpoint Thermostat/sensor fault or wrong mode/schedule Any engineer or competent customer
Ices up on the indoor coil Low airflow, low refrigerant charge, or faulty expansion device Airflow: any engineer. Refrigerant: F-Gas certified only
Low or falling cooling performance over weeks/months Slow refrigerant leak (undercharge) F-Gas certified engineer only
Compressor hums but doesn't start, or trips on start Capacitor, contactor or overload fault Qualified electrical/AC engineer
Outdoor unit not running at all No power, isolator tripped, control fault Electrician or AC engineer
Hissing/bubbling noise, oily residue at a joint Refrigerant leak F-Gas certified engineer only
Excessive noise, vibration, no cooling drop Fan motor or bearing fault (indoor or outdoor) AC engineer

Detailed Guidance

Fault-Finding Decision Tree

START: Customer reports "AC not cooling"
│
├─ STEP 1: Is the system running at all? (indoor unit fan, outdoor unit fan/compressor)
│   ├─ NO — nothing runs
│   │   ├─ Check power supply / isolator / RCD / breaker tripped
│   │   │   ├─ Tripped repeatedly → electrical fault (compressor, capacitor, wiring) — call AC/electrical engineer
│   │   │   └─ Reset holds → monitor; check thermostat call for cooling
│   │   └─ Check thermostat/controller: correct mode (cooling, not fan/heat), setpoint below room temp, schedule not blocking
│   │       ├─ Controller fault / dead batteries / no display → replace/reset controller
│   │       └─ Controller fine, system still won't start → call AC engineer (control board or contactor fault)
│   │
│   └─ YES — something is running
│       ├─ STEP 2: Is the INDOOR fan blowing air?
│       │   ├─ NO airflow at all → check filter fitted correctly, fan speed setting, blower fault → any engineer
│       │   └─ YES, air is moving → proceed to Step 3
│       │
│       ├─ STEP 3: Is the air coming out WARM or only slightly cool (not properly cold)?
│       │   ├─ Check filter — is it visibly blocked/dirty?
│       │   │   ├─ YES → clean/replace filter, re-test after 15–20 min
│       │   │   └─ NO → proceed
│       │   ├─ Check OUTDOOR unit — is the coil clean and clear (no leaves/debris/ice)?
│       │   │   ├─ Blocked/dirty coil → clean coil, check clearances, re-test
│       │   │   ├─ Coil iced up → is it defrosting normally, or staying iced?
│       │   │   │   ├─ Melts within 15–20 min after stopping → likely airflow-related, monitor
│       │   │   │   └─ Stays iced / re-ices quickly → possible low refrigerant charge or expansion valve fault → F-Gas certified engineer
│       │   │   └─ Coil clean, no ice, fan running normally → proceed
│       │   └─ Check temperature differential at indoor unit (supply vs return)
│       │       ├─ Differential well below ~10°C, all airflow checks clear → refrigerant-side fault suspected → F-Gas certified engineer to check pressures, superheat/subcooling
│       │       └─ Differential normal but room still doesn't reach setpoint → check system sizing, room heat gains, or thermostat sensor placement
│       │
│       └─ STEP 4: Has the system stopped ON ITS OWN mid-cycle, or shows a fault code?
│           ├─ Water visible near indoor unit / drain pan → check condensate drain and pump
│           │   ├─ Blocked drain/tray → clear and flush, check fall, re-test
│           │   └─ Condensate pump failed (float switch/non-return valve) → replace/repair pump
│           ├─ Fault code on display → look up code in manufacturer's manual
│           │   ├─ Code indicates sensor/electrical fault → qualified engineer, no refrigerant access needed
│           │   └─ Code indicates pressure/refrigerant fault → F-Gas certified engineer required
│           └─ No code, just stopped → check for overheat/high-pressure protection trip (blocked condenser, high ambient) → clear obstruction, allow to cool, reset
│
└─ If all airflow, controls and condensate checks are clear and performance is still poor:
    → Escalate to an F-Gas certified engineer for pressure, superheat/subcooling and leak-detection checks.
      Do not attempt to connect gauges, recover, or add refrigerant without F-Gas certification —
      this is a legal requirement, not best practice.

Airflow restriction — the most common cause

Start every "not cooling" call-out here — it accounts for a large share of genuine faults and needs no refrigerant access. A blocked evaporator (indoor) filter reduces airflow across the coil and can cut rated cooling capacity by 15–25% within a single season if neglected — the system runs, blows air, but that air is only mildly cool. Check and clean or replace the filter first, always, before assuming anything more serious.

Equally common and equally overlooked: the outdoor condenser coil, where the system actually rejects the heat pulled from inside. If it's clogged with leaves, cottonwood, insect debris or general dirt, the whole system struggles regardless of how clean the indoor filter is. Check the manufacturer's minimum clearances (commonly around 300mm rear, 1m front — confirm against the specific installation manual) haven't been compromised by fencing or planting, and clean the coil fins with a coil cleaner or a fin comb if bent.

Condensate drainage — the "stopped cooling" that isn't a cooling fault at all

A large proportion of "the AC just stopped" call-outs aren't cooling faults at all — they're the system protecting itself from an internal water overflow. Most split systems have a float switch in the condensate tray or pump that shuts the compressor down if condensate can't drain away, whether the tray or drain line is blocked with biofilm and dust, or a condensate pump has failed (stuck float switch, failed non-return valve, or a burned-out pump). This presents exactly like a refrigerant or compressor fault — "it was cooling fine, then it just stopped" — but is resolved by clearing and flushing the drain path or replacing the pump, with no refrigerant work involved.

Thermostat and controls faults

Before assuming a mechanical or refrigerant fault, rule out the controller. Check the system is actually in cooling mode (not fan-only or heating on a reversible unit), the setpoint is genuinely below room temperature, no active schedule or "away" mode is overriding the manual setting, and battery-powered wall controllers aren't flat. On smart or zoned multi-split systems, check that a master controller or zone damper isn't blocking flow to the room. These faults are common, quick to diagnose, and cost the customer nothing beyond the call-out.

Icing, low charge and when to call an F-Gas engineer

Ice forming on the indoor coil is a classic symptom with several possible causes. Restricted airflow (a blocked filter, closed vents, or a failing indoor fan) is the most common and cheapest to fix — clear the airflow path and the icing should resolve within a normal defrost cycle. Persistent or rapidly recurring icing, especially alongside falling cooling performance over weeks or months, points toward a genuine refrigerant undercharge from a slow leak, or an expansion valve fault. At this point the job crosses the legal line: only an F-Gas certified engineer may connect gauges to check suction and discharge pressures, calculate superheat and subcooling against manufacturer targets, leak-test the system, and — if confirmed — recover and recharge refrigerant, weighed on calibrated scales and logged in the F-Gas record. See f gas regulations guide for certification and record-keeping requirements, and refrigerant types comparison for how R32 and R410A behave differently in fault conditions.

Electrical faults

A compressor that hums but won't start, or trips the breaker on start-up, is very often an electrical fault — a failing run capacitor, a worn contactor, or an overload trip — rather than a refrigerant problem. This work requires safe isolation under the Electricity at Work Regulations 1989 before any panel is opened, and diagnosis (capacitor testing, contactor inspection, motor winding checks) sits with a qualified electrical or AC engineer. Don't default to "it needs re-gassing" just because the outdoor unit isn't running — confirm power reaches the compressor and the electrical components are sound before considering the refrigerant circuit at all.

When to escalate immediately

Some symptoms should go straight to an F-Gas certified engineer without further general-trade diagnosis: a hissing or bubbling noise at a pipe joint, visible oily residue around a fitting (oil circulates with refrigerant, so a residue is a classic leak sign), or a fault code that explicitly references pressure or refrigerant. These are refrigerant-circuit symptoms from the outset and don't benefit from filter or condensate checks first.

Frequently Asked Questions

Can I check refrigerant levels myself if I'm not F-Gas certified?

No. Connecting gauges to the refrigerant circuit, checking pressures, or adding or recovering refrigerant in any quantity is restricted to F-Gas certified technicians under the Fluorinated Greenhouse Gases Regulations. This applies regardless of system size or refrigerant type — R32 and R410A are both covered. A general engineer or electrician can rule out every non-refrigerant cause (filters, condenser fouling, condensate, controls, electrical faults) but must hand off to a certified engineer once refrigerant work is genuinely needed.

The system is icing up — does that always mean low refrigerant?

No. Icing is most commonly caused by restricted airflow — a blocked filter, closed or obstructed vents, or a failing indoor fan — which is a straightforward, unrestricted fix. Persistent or rapidly recurring icing that doesn't resolve once airflow is confirmed clear is the point at which a refrigerant undercharge or expansion valve fault becomes the likely cause, and that diagnosis (pressure and superheat/subcooling checks) requires an F-Gas certified engineer.

Why did the system just stop running with no warning?

Check the condensate drain and pump before assuming a mechanical failure. Many systems shut the compressor down automatically via a float switch if condensate can't drain away, to prevent an internal water overflow — this is the system working correctly, not a fault with the cooling components themselves. Clearing a blocked drain or fixing a failed condensate pump resolves a large share of these "sudden stop" call-outs with no refrigerant work involved.

How much cooling capacity can a dirty filter or condenser actually cost?

A blocked evaporator filter alone can cut rated cooling capacity by roughly 15–25% within a single season of neglect. A fouled outdoor condenser coil compounds this further, because the whole system depends on the outdoor coil to reject the heat pulled from inside — restricted airflow there degrades performance across the board, independent of the filter condition indoors.

Is it worth trying a reset before calling an engineer?

Yes, as a first step for a system that has stopped without obvious cause: check the thermostat mode and setpoint, confirm the isolator or breaker hasn't tripped, and power-cycle the unit per the manufacturer's instructions. If the fault clears and doesn't recur within 24 hours, it was likely transient. If it recurs, or a fault code reappears, book a proper diagnostic visit rather than repeatedly resetting a genuine fault.

Regulations & Standards