Electrical Supply for Workshops and Outbuildings: Sub-board, SWA Cable and PME Earthing
Quick Answer: A workshop or outbuilding supply requires a maximum demand calculation, SWA submain sized for the load and voltage drop (typical 10mm² 3-core for 40A over 30m), a sub-consumer unit at the outbuilding with main switch and circuit protection, and careful earthing — the PME (TN-C-S) earth from the supply must NOT be exported to most outbuildings under BS 7671:2018+A2:2022 Regulation 411.4.5, so a local TT earth electrode with whole-supply 30mA RCD protection is usually required. The work is notifiable under Building Regulations Part P.
Summary
Powering an outbuilding — garage, workshop, garden office, summerhouse — is one of the most common electrical installation jobs after consumer unit replacement, and one of the most consistently done wrongly. The cable run is straightforward and the consumer unit at the destination is just a smaller version of a domestic board. What trips most installers is the earthing arrangement.
Most UK domestic supplies are TN-C-S (PME — Protective Multiple Earth), where the supplier combines neutral and earth into a single conductor in the supply cable. The DNO requires the neutral to be earthed at multiple points along the network. This system works well inside buildings, but exporting the PME earth to a detached outbuilding creates a serious risk: if the supply neutral becomes open-circuit (broken neutral fault), the consumer's earthed metalwork — including taps, radiators, gas pipework, and the outbuilding's metallic surfaces — can rise to mains potential. Anyone touching that metalwork while standing on earth outside is connected directly across mains.
This article walks through the design of an outbuilding supply: maximum demand calculation, SWA submain selection, sub-consumer unit configuration, and the critical earthing decision — when to use the PME earth, when to use a local TT electrode, and how to apply BS 7671:2018+A2:2022 Regulation 411.4.5 in practice. For cable specifics see armoured cable and for general sizing see cable sizing.
Key Facts
- Maximum demand calculation — sum diversified loads: lighting + 16A general sockets + dedicated appliances; typical small workshop 25–40A, medium 40–63A, large or 3-phase 63A+
- Submain cable — almost always SWA (BS 6346 PVC/PVC or BS 5467 XLPE/PVC); 6mm² for ~32A short runs, 10mm² for ~40A, 16mm² for 50–63A, 25mm² for 80–100A
- Voltage drop limit — BS 7671 Appendix 12: 3% for lighting, 5% for other circuits (combined from origin of installation, including submain + final circuit)
- Submain protection — at the main consumer unit, typically an MCB or RCBO matching submain current rating
- Sub-consumer unit at outbuilding — incoming isolator (DP main switch or DP RCD), busbar, MCBs or RCBOs for individual final circuits
- BS 7671:2018+A2:2022 Reg 411.4.5 — restricts use of PME (TN-C-S) earthing for outdoor installations and outbuildings where touch-voltage hazard exists
- BS 7671 Reg 411.3.1.2 — main protective bonding requirements
- TT alternative — local earth electrode at the outbuilding, whole-supply 30mA RCD, no PME earth exported
- Earth electrode minimum — typically a single 1.2m or 2.4m copper-bonded steel rod; achieve <200Ω earth resistance (BS 7671 Reg 411.5.3)
- BS 7430:2011+A1:2015 — earthing of electrical installations (code of practice)
- Three-phase requirement — typically needed for loads >100A single-phase, large 3-phase machines (planers, lathes >5kW), or for power factor reasons
- Part P notifiable in England — installation of a new circuit (which includes a submain to an outbuilding) is notifiable work
- Grouping factor for SWA — XLSI / XLPE buried cable; refer to BS 7671 Appendix 4 Table 4C5 if multiple cables grouped
- UK national rate fallback — when quoting, use trade-appropriate rate: Electrician £60/hr where company has not set custom rates
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →| Workshop Type | Estimated Demand | Submain Cable | Submain MCB | Sub-CU Size |
|---|---|---|---|---|
| Garden shed — lights + 1 socket | 6A | 2.5mm² 2c SWA | 16A | 2-way |
| Garden office — lights + sockets + heater | 16A | 4mm² 3c SWA | 20A | 4-way |
| Small workshop — bench tools + 2x sockets + light | 25A | 6mm² 3c SWA | 32A | 6-way |
| Medium workshop — tablesaw + sockets + dust extractor | 40A | 10mm² 3c SWA | 40A | 8-way |
| Large workshop — multiple machines, welder, compressor | 63A | 16mm² 3c SWA | 63A | 12-way |
| Three-phase workshop — industrial machines | 80–100A 3φ | 25mm² 4c SWA | 80A TPN | 12-way TPN |
| Detached garage (no workshop) | 16–32A | 4–6mm² 3c SWA | 20–32A | 4–6 way |
Detailed Guidance
Step 1: Maximum Demand Calculation
Maximum demand is the diversified estimate of the simultaneous load — not the sum of all rated loads. Lighting circuits rarely operate at full lamp count; sockets are not all in use at once. Apply diversity per IET On-Site Guide Table 1A and BS 7671 Appendix 1.
Worked example — small workshop:
| Load | Rated | Diversity | Diversified |
|---|---|---|---|
| Lighting (4× 60W LED) | 1A | 100% | 1A |
| 2× 13A socket spurs | 26A | 30% | 8A |
| Dust extractor 1.5kW | 7A | 100% | 7A |
| Bench grinder 300W | 1.3A | 50% | 0.65A |
| Tablesaw 2.2kW | 10A | 100% | 10A |
| Total | 26.65A |
Round up for headroom — specify a 32A submain. The sub-CU needs a 6/10A lighting circuit, 20A radial or 32A ring for general sockets, a dedicated 16/20A circuit for the tablesaw with workshop isolator, and a spare way for future expansion.
Step 2: Submain Cable Sizing
Voltage drop check (most common limiting factor):
For 32A over 30m on 6mm² SWA:
- mV/A/m for 6mm² (BS 7671 Appendix 4 Table 4D4B) = 7.3
- Vd = 7.3 × 32 × 30 / 1000 = 7.0V
- 7.0V / 230V = 3.04%
- Plus 1.5% final circuit voltage drop in workshop = ~4.5% total
- Below 5% limit → acceptable, but tight
Better: 10mm² for the same circuit
- mV/A/m for 10mm² = 4.4
- Vd = 4.4 × 32 × 30 / 1000 = 4.2V = 1.84%
- Plenty of headroom for future load growth
Earth fault loop impedance:
- For a 32A Type B MCB protecting a TN-C-S circuit, max Zs per BS 7671 Table 41.3 = 1.44Ω
- Ze (typical TN-C-S) = 0.35Ω
- R1+R2 must be < 1.09Ω
- 10mm² 3c SWA with armour earth: R1+R2 ≈ 0.02Ω/m → 30m = 0.6Ω → margin OK
Current rating check:
- 10mm² SWA Method D direct buried: 64A (BS 7671 Table 4D4A)
- 32A design current well within rating → no derating needed
For full sizing methodology including grouping factors and ambient temperature corrections, see cable sizing.
Step 3: The Earthing Decision — PME vs TT
This is the most important decision in the design and the most commonly mishandled.
Outbuilding earthing — decision tree
┌─────────────────────────────────────────────────┐
│ What is the supply earthing arrangement at │
│ the main building? │
└──────────────────┬──────────────────────────────┘
│
┌──────────▼──────────┐
│ TN-S (separate │
│ earth conductor)? │
└──────┬──────────┬───┘
│YES │NO
│ │
┌───────────▼──┐ ┌───▼──────────┐
│ Can export │ │ TN-C-S (PME) │
│ earth to │ │ or TT? │
│ outbuilding │ └───┬──────┬───┘
│ via SWA │ │TN-CS │TT
│ armour │ │ │
└──────────────┘ │ │
┌───────▼──┐ ┌▼────────────┐
│Does the │ │Already TT— │
│outbuilding│ │export TT │
│have any │ │earth or │
│outdoor │ │provide local│
│earthable │ │electrode │
│metalwork │ │ │
│people │ │ │
│can touch?│ │ │
└───┬───┬──┘ └─────────────┘
│YES│NO
│ │
┌───────▼─┐ ▼────────────────┐
│MUST use │ │Can export PME │
│TT — │ │if no exposed │
│local │ │extraneous │
│earth rod│ │metalwork — but │
│+ whole │ │TT often safer │
│supply │ │choice │
│30mA RCD │ │ │
└─────────┘ └─────────────────┘
The PME (TN-C-S) problem in plain English:
In a PME system, the supply neutral is also the earth. The DNO earths it at the substation and at multiple poles along the LV network. Under normal operation this provides a low-impedance earth path.
If the supply neutral becomes open-circuit (a "broken neutral" fault — a corroded joint at a pole, a cable fault, sometimes upstream of multiple properties), then:
- All connected load current returns through the earth bonding of the affected property
- The "earth" can rise to a significant fraction of mains voltage above true ground
- Any earthed metal — taps, radiators, central heating, garage door rails — sits at this elevated potential
- A person touching that metal while standing on true ground (outside on grass or paving) becomes the path for current to flow
Inside a building, this risk is mitigated by main protective bonding (Reg 411.3.1.2) — all extraneous-conductive parts are bonded together so everyone touching them is at the same potential. Outside, you cannot bond grass and tarmac. The hazard is real and has caused fatalities.
Regulation 411.4.5:
BS 7671:2018+A2:2022 prohibits the use of TN-C-S (PME) earthing where there is a significant risk of broken neutral creating a touch voltage hazard. The judgement call is whether the outbuilding has external metalwork that a person could touch while standing on true earth.
Practical guidance:
- Detached garage with concrete floor, metal door, metallic cladding, metal door frame: TT (local earth rod, whole-supply 30mA RCD) is the correct choice
- Garden office with timber construction, no exposed external metalwork, no extraneous-conductive parts: PME export is technically permissible but TT is still safer practice
- Outbuilding with metal water supply pipe entering the ground: the water pipe is an extraneous-conductive part bonded to local earth — if this is bonded to the supply PME earth, the broken-neutral fault propagates to the pipe. TT is required.
- Greenhouse, garden shed in contact with soil, swimming pool plant room: TT only.
TT installation requirements:
- Local earth electrode at the outbuilding — copper-bonded steel rod, 1.2m or 2.4m long, achieving <200Ω earth resistance (BS 7671 Reg 411.5.3 minimum; <100Ω is good practice for reliable RCD operation)
- Bond rod via insulated 16mm² green/yellow to the sub-consumer unit earth bar
- Sub-CU incoming main switch must be a 30mA RCD (or upstream 100mA time-delayed RCD with 30mA RCDs on individual circuits)
- The SWA submain's armour must NOT be bonded to the outbuilding's earth at the gland — only to the supply's earth at the main consumer unit
A common error: running 3-core SWA with full gland bonding at both ends, then "adding" a local earth rod. This creates a parallel earth path — a broken neutral fault energises the local TT earth via the supply armour, rendering the TT earth useless. The supply earth MUST be electrically separated from the local TT earth at the outbuilding for TT to function correctly.
Step 4: Sub-Consumer Unit at the Outbuilding
The sub-consumer unit (sub-CU) is a small consumer unit at the outbuilding, fed from the submain.
Configuration for TT outbuilding (most common): 63A/80A DP 30mA RCD as main switch (provides shock protection given the TT earth), standard DIN rail busbar, final circuits comprising 6A/10A Type B MCB for lighting, 32A or 20A Type B for sockets, and a 16A/20A MCB with workshop isolator for dedicated machines. Earth bar connects to the local electrode by 16mm² G/Y. Neutral bar is NOT bonded to earth — bonding it would defeat the TT arrangement.
Configuration for TN-S exported earth (rare): plain DP isolator as main switch, RCBOs (Type A/F) on individual final circuits, earth bar from the incoming PE conductor.
Configuration for TN-C-S exported earth (only where external touch-voltage risk is genuinely absent): plain DP isolator or 100mA time-delayed RCD; comprehensive main protective bonding of all extraneous-conductive parts (water, gas, structural steel). TT is usually the safer choice — TN-C-S export is rarely the right answer.
Step 5: Three-Phase Considerations
Most domestic outbuildings are single-phase. Three-phase becomes necessary for:
- Large industrial machines (lathes, planers, mills above ~5kW)
- High-current loads (50A+ continuous)
- Welders rated above ~7kW
- Multiple machines in simultaneous operation
Three-phase supply requirements:
- Confirm with DNO whether 3-phase is available at the property — domestic supplies are usually single-phase, upgrade to 3-phase requires DNO involvement and may incur cost
- 4-core SWA submain (3 phases + neutral); armour as CPC, or 5-core (3 phases + neutral + earth) where supplementary earth conductor specified
- Three-phase consumer unit (TPN — three-phase + neutral) with appropriate isolator
- Balance loads across phases as far as possible
- Three-phase RCD protection — Type B RCDs if connected loads include variable-frequency drives (VFDs) with DC fault current potential, otherwise Type A
Step 6: Part P Notification
In England, installing a submain to an outbuilding constitutes a new circuit and is notifiable under Building Regulations Approved Document P:
- Registered competent person (NICEIC, NAPIT, ELECSA, Stroma) — self-certifies via scheme portal
- Building control — submit Building Notice and have local building control inspect
- Third-party verification — independent registered inspector certifies after work complete
For Wales: equivalent under Welsh Approved Document P. For Scotland: Building (Scotland) Regulations Section 4.5. For Northern Ireland: Building Regulations Part F.
Specifically notifiable for outbuildings:
- Garage, garden office, summerhouse new circuit
- Garden lighting on new circuit
- Outdoor sockets on new circuit
- Greenhouse heating circuit
- Pond/pool installation (special location)
Frequently Asked Questions
Why can't I just use the PME earth like I do inside the house?
Inside a house, all earthed metalwork is bonded together via main protective bonding — water pipe, gas pipe, structural metalwork. Anyone inside touching earthed metal is at the same potential as everything else. Outside, you cannot bond the grass and the patio to the earth bar. If the PME neutral breaks, the earthed metal of a detached garage rises to mains potential, but the ground around it does not. A person standing on the ground and touching the garage becomes the current path. This has caused several UK fatalities — BS 7671 Reg 411.4.5 exists specifically to prevent it.
What earth resistance do I need on a TT earth electrode?
BS 7671 Reg 411.5.3 sets a maximum of 1666Ω for a 30mA RCD (RA × IΔn ≤ 50V) but recommends much lower in practice — typically <200Ω for reliable RCD operation across all fault scenarios. In good soil, a single 1.2m rod will achieve <100Ω. In rocky or sandy ground, multiple rods or a deeper rod may be needed. Test with an earth electrode resistance tester after installation and record on the Electrical Installation Certificate.
Can I run the SWA above ground on cable cleats instead of burying it?
Yes, SWA can be surface-mounted on a wall or fence with cleats at appropriate intervals (manufacturer guidance, typically ~600mm cleat spacing for 6mm² and below, 400mm for larger sizes). However, exposed SWA needs UV-stable sheath — BS 6346 standard PVC sheath has limited UV resistance; specify UV-stable PVC or PE outer sheath for sun-exposed runs. Mechanical protection from impact is also a consideration — buried is generally more robust long-term.
How long can a submain be before voltage drop becomes an issue?
For 32A on 10mm² SWA, voltage drop is about 1.4V per 10m. Allowable drop on submain alone might be 2.5–3% (5.7–6.9V) to leave headroom for the final circuit, so 40–50m on 10mm². Beyond that, step up to 16mm² (mV/A/m = 2.8) which extends the run substantially. For very long runs (>100m) consider 3-phase to reduce currents by √3, or simply oversize the cable significantly. There is no regulatory maximum length — voltage drop is the practical limit.
Do I need an external isolator at the outbuilding for the DNO?
The DNO requirement is for an isolator accessible to them at the supply origin — that is the main consumer unit, not the outbuilding. However, a clearly-labelled external isolator at the outbuilding (or just inside the door) is good practice for the user — for maintenance, emergency, or in case of fire. A DP 63A switch-fuse outside the building, locked when not in use, is a sensible specification.
Regulations & Standards
BS 7671:2018+A2:2022 — IET Wiring Regulations 18th Edition Amendment 2; particularly:
- Reg 411.3.1.2 (main protective bonding)
- Reg 411.4.5 (PME earthing restrictions)
- Reg 411.5.3 (TT earth electrode resistance)
- Section 522 (selection and erection — environmental influences)
- Section 705 (agricultural and horticultural premises — relevant to outbuildings on farms)
BS 7430:2011+A1:2015 — Code of practice for protective earthing of electrical installations
BS 6346 / BS 5467 / BS 6724 — SWA cable standards (see armoured cable)
ENA EREC G81 — Energy Networks Association framework for design of low-voltage underground networks
ENA EREC G87 — guidance on PME export and the broken neutral hazard
Building Regulations Approved Document P — England (electrical safety in dwellings)
Building Regulations Approved Document P (Wales) — Wales equivalent
Building (Scotland) Regulations Section 4.5 — Scotland equivalent
IET On-Site Guide — diversity factors (Table 1A) and practical design guidance
IET Guidance Note 8 (Earthing & Bonding) — practical TT and PME guidance
Energy Networks Association — Combined Neutral and Earth (PME) Guidance
NICEIC Technical Information — TT vs TN-C-S outbuilding earthing
NAPIT Technical Bulletins — sub-board and submain specification
armoured cable — SWA cable selection, burial, and gland termination
cable sizing — full sizing methodology including voltage drop and Zs
consumer units — consumer unit selection (the sub-CU at the outbuilding)
consumer unit upgrade — at the main building, integrating the outbuilding submain
safe isolation procedure — for working at either end of the submain