Summary
The FCU is the accessory that turns a socket circuit into a safe supply for things that should not be on a plug: boilers, cooker hoods, waste disposers, towel rails, outside lights, extractor fans, under-cupboard lighting, alarm panels and the fused feed for a run of extra sockets. It does three things at once. The fuse protects the smaller cable or flex on the load side, which is the only reason a 1.5 mm² cable can hang off a 32 A ring. The switch, where fitted, gives a local point of isolation for cleaning and maintenance of the appliance. And the terminals give a proper fixed connection instead of a plug that can be pulled out or an appliance left wired into a socket back box.
The confusion on site is usually about spurs rather than FCUs. "Spur" means a branch cable off a ring final or radial, and the regulations distinguish sharply between an unfused spur, which stays in the ring's 2.5 mm² cable and is limited to one point, and a fused spur, which passes through an FCU and can then feed as many points as the 13 A fuse will sensibly supply. The limits are in Appendix 15 of BS 7671 and in the IET On-Site Guide, and they exist because a ring final circuit relies on the load being spread around the ring; too many unfused spurs defeat that, and a long run of sockets on an unfused spur is an overload waiting to happen.
The third source of trouble is where the FCU goes. An FCU in a bathroom zone, an FCU feeding an immersion heater from a kitchen ring, or a cooker hood FCU buried behind the hood with no way to reach it all come up on condition reports as C2 or C3 observations. This article sets out when an FCU is the right answer, what fuse to fit, how to wire the three common arrangements and where the regulations draw the line.
Key Facts
- BS 1363-4:2016+A1:2018 — the product standard for 13 A fused connection units, switched and unswitched; the fuse is a BS 1362 cartridge, available in 3 A, 5 A, 13 A and other ratings
- Unfused spur (Appendix 15) — 2.5 mm² from a ring final circuit, feeding one single or twin socket-outlet or one FCU; connected at a socket, at a junction box in the ring, or at the origin in the consumer unit
- Number of unfused spurs — the On-Site Guide advises that the number of unfused spurs should not exceed the number of socket-outlets and fixed appliances connected directly in the ring
- Fused spur — taken through an FCU; the load side is protected by the fuse, so it may feed any number of socket-outlets or fixed points and the outgoing cable is sized to the fuse rating
- Outgoing cable — must have a current-carrying capacity not less than the fuse rating under the installation method used; 1.5 mm² is the accepted minimum behind a 13 A fuse, and 1.0 mm² behind a 3 A or 5 A fuse where the installation method permits
- Fuse selection — 3 A for loads up to roughly 700 W (boilers, controls, alarm panels, small fans, LED lighting); 13 A for loads above that (towel rails, heaters, waste disposers); 5 A is used by some manufacturers' instructions for specific appliances
- Switched FCU — provides the local switch required by Regulation 537.3 for mechanical maintenance of fixed equipment; must be double-pole where it is the means of isolation for the appliance
- Unswitched FCU — used where the switching is provided elsewhere (a boiler with its own isolator, or an appliance with its own control) or where accidental switch-off must be avoided
- Neon indicator — optional; useful on boilers, outside lights and freezers to show the supply is present
- Flex outlet — an FCU with a flex outlet (front or bottom entry) takes the appliance flex directly, with a cord grip; alternatively use a separate flex outlet plate fed from the FCU
- Loads that should not be spurred — immersion heaters, instantaneous water heaters, electric showers, cookers above 2 kW, comprehensive space heating, and any single load above 2 kW, which should have a dedicated circuit (Appendix 15 and Regulation 433.1.204)
- Bathrooms (Section 701) — no FCU or switch in zones 0, 1 or 2 except SELV and shaver units; a switched FCU for a towel rail or fan goes outside the zones, and socket-outlets must be at least 3 m horizontally from the boundary of zone 1
- Accessibility — an FCU used as a means of isolation must be accessible after the appliance is fitted; behind a built-in oven or a cooker hood with no cut-out is a C3 observation and poor practice
- RCD protection — a new spur in 2.5 mm² buried in a wall at less than 50 mm needs 30 mA RCD protection (Regulation 522.6.202) unless it is in earthed metal conduit or an earthed metal-sheathed cable; socket-outlets up to 32 A need 30 mA RCD protection anyway (Regulation 411.3.3)
- Certification — a new spur or FCU on an existing circuit is a Minor Electrical Installation Works Certificate; it is not notifiable in England unless in a bathroom zone (see electrical certificates eic mwc eicr explained)
- Heights — in new dwellings, switches and controls between 450 mm and 1,200 mm from floor level (Approved Document M, Part M4(1))
- Earthing — the FCU earth terminal must be connected; a metal-plate FCU on a metal back box relies on the fixing screws and the earth tail
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →| Appliance or load | FCU type | Fuse | Outgoing cable (typical) | Notes |
|---|---|---|---|---|
| Gas or oil boiler | Switched, often with neon | 3 A | 1.0–1.5 mm² or 0.75 mm² flex | Many manufacturers specify 3 A; check the MI |
| Cooker hood | Switched | 3 A | 1.0–1.5 mm² | Must be accessible after the hood is fitted |
| Waste disposer | Switched, double-pole | 13 A | 1.5 mm² | Switch within reach but not where it can be knocked |
| Heated towel rail | Switched, double-pole | 3 A or 13 A to suit the rating | 1.5 mm² | FCU outside bathroom zones |
| Extractor fan (bathroom) | Switched (3-pole isolator usually needed in addition for a timer fan) | 3 A | 1.0 mm² | Isolator for maintenance outside zones |
| Outside light | Switched with neon | 3 A | 1.5 mm² | FCU indoors, light fed through the wall |
| Under-cupboard LED lighting | Switched | 3 A | 1.0 mm² | Driver may sit above the units |
| Intruder alarm or fire panel | Unswitched, often with neon | 3 A | 1.0 mm² | Unswitched to prevent accidental loss of supply |
| Fused spur to extra sockets | Switched or unswitched | 13 A | 2.5 mm² or 1.5 mm² | Any number of sockets on the load side |
| Freezer in a garage | Unswitched with neon | 13 A | 1.5 mm² | Consider a dedicated circuit to avoid RCD nuisance loss |
| Electric shower, immersion heater, cooker over 2 kW | Not an FCU | — | — | Dedicated circuit required |
Detailed Guidance
Unfused spur, fused spur and FCU: the three arrangements
RING FINAL CIRCUIT (32 A, 2.5 mm²)
│
├─ UNFUSED SPUR
│ Ring socket ──2.5 mm²──> ONE socket (single or twin) or ONE FCU
│ No fuse in the spur. Limited to one point. Cable stays 2.5 mm².
│
├─ FUSED SPUR
│ Ring socket ──2.5 mm²──> FCU (13 A fuse) ──1.5 mm² or 2.5 mm²──> socket ──> socket ──> socket
│ Fuse limits the load, so any number of points on the load side.
│
└─ FCU FEEDING A FIXED APPLIANCE
Ring socket ──2.5 mm²──> Switched FCU (3 A or 13 A) ──flex or 1.5 mm²──> flex outlet / appliance
FCU gives fusing, local switching and a fixed connection.
The same three arrangements apply on a 20 A or 32 A radial, with the difference that a radial has no "one point" rule for unfused spurs: a branch in the same size cable as the radial is simply part of the radial, provided the circuit's total load and length remain within its design.
Wiring the FCU
An FCU has two pairs of terminals plus earth. Supply (or "Feed", "In", "Mains") takes the cable from the ring or radial; on a fused spur that cable is 2.5 mm². Load (or "Out") feeds the appliance or the sockets beyond; this side is protected by the fuse. Connect the earth to the back box terminal and to the accessory's earth terminal, with a sleeved tail between them on a metal box.
Three things go wrong repeatedly:
- Supply and load swapped. The fuse then protects nothing on the load side, and on a switched FCU the appliance stays live with the switch off. Check the markings; they vary between makes.
- Looping the ring through the FCU. Both ring legs land in the supply terminals. BS 1363-4 terminals are rated for this with 2.5 mm² and it is permitted, but many FCU supply terminals are tight with two 2.5 mm² conductors, and the ring continuity now depends on an accessory terminal. Where the layout allows, spur the FCU from a socket or a junction box instead.
- Flex clamped under a terminal screw with no ferrule, or pulled out of a plate with no cord grip. Use the cord grip on a flex-outlet FCU, or a separate flex outlet plate.
On a switched FCU for a fixed appliance the switch must break the line conductor and, where it is the means of isolation for the appliance, both line and neutral (double-pole). Most switched FCUs sold in the UK are double-pole; some cheaper "switched" units break line only, so check the data sheet before using one as an isolator.
Choosing the fuse
The fuse protects the flex and the load-side cable, not the appliance's internal electronics. Size it to the appliance rating and the manufacturer's instructions:
- 3 A: up to about 700 W — boilers, fans, alarm panels, lighting, cooker hoods, most electronic appliances
- 5 A: where the manufacturer specifies it, for loads between 700 W and about 1,150 W
- 13 A: above about 700 W where no 5 A is specified — towel rails up to 3 kW, waste disposers, small heaters, fused spurs to sockets
A boiler on a 13 A fuse with 0.75 mm² flex is a common error; the flex is protected by the fuse, and 0.75 mm² flex is rated well below 13 A. Fit the fuse the manufacturer's instructions specify. If the instructions are silent, size the fuse to the flex or cable, not the appliance.
The limits in Appendix 15
Appendix 15 is informative rather than a regulation in itself, but it sets the accepted design for ring final circuits in domestic premises and the competent person schemes assess against it:
- A ring final circuit in 2.5 mm² on a 30 A or 32 A device may serve an unlimited number of socket-outlets within a floor area of about 100 m², provided the load is spread around the ring
- An unfused spur in 2.5 mm² may feed one single or one twin socket-outlet or one FCU
- An unfused spur may be connected at the terminals of a socket-outlet, at a junction box, or at the origin of the circuit in the consumer unit
- The number of unfused spurs should not exceed the total number of socket-outlets and fixed appliances connected directly in the ring
- A fused spur through an FCU may feed any number of points, with the outgoing cable sized to the fuse (minimum 1.5 mm² in practice for 13 A)
- Loads above 2 kW, immersion heaters, comprehensive space heating and instantaneous water heaters should be on dedicated circuits
Regulation 433.1.204 is the formal basis: it permits the 32 A device on a 2.5 mm² ring on the condition that the installed load, including any spurs, is reasonably shared around the ring so that no part carries more than its current-carrying capacity for long periods.
Bathrooms and kitchens
In a bathroom, Section 701 permits no switches or controls in zones 0, 1 or 2 other than SELV, shaver units to BS EN 61558-2-5 and the cord of a pull switch. A switched FCU for a towel rail, a fan or an electric underfloor heating thermostat therefore sits outside the zones, usually outside the door or on the landing, and the appliance is fed through the wall. Socket-outlets in a bathroom must be at least 3 m horizontally from the zone 1 boundary, which in most UK bathrooms means none at all.
In a kitchen, the common problem is access. An FCU behind a built-in oven, behind a dishwasher or above a cooker hood where it cannot be reached without removing the appliance does not satisfy Regulation 537.3's requirement for a readily accessible means of switching off for mechanical maintenance. Fit the switched FCU above the worktop, and use a flex outlet or an unswitched FCU behind the appliance if a second connection point is needed. Grid switches labelled for each appliance are a tidy alternative above the worktop.
Cooker hoods, fans and 3-pole isolation
A cooker hood is a fixed appliance and the FCU is its means of switching off. A bathroom extractor fan with a timer run-on has three conductors on the supply side (permanent live, switched live, neutral) and needs a 3-pole fan isolator outside the zones so that a maintainer can isolate all of them; a 3 A FCU on the permanent live alone does not isolate the switched live from the light switch. Fit the fan isolator and, where the fan is fed from a lighting circuit, a 3 A FCU is usually unnecessary because the 6 A lighting circuit protective device already protects a 1.0 mm² cable.
Outbuildings and freezers
Freezers in garages are often put on a fused spur with a neon FCU so that a tripped RCD or a knocked switch is visible. A better arrangement where the budget allows is a dedicated radial on its own RCBO, so that a fault elsewhere on a shared RCD does not thaw the contents. Either way, a freezer should not be on a switched FCU that can be turned off in passing; use an unswitched unit with a neon.
Testing and certification
A new spur or FCU is an addition to an existing circuit and gets a Minor Electrical Installation Works Certificate. Test: continuity of the protective conductor to the new point (R1+R2), insulation resistance of the new cable, polarity at the FCU and at every point on the load side, earth fault loop impedance Zs at the furthest new point, and RCD operation where the circuit is RCD-protected. On a fused spur check that Zs at the furthest socket is within the limit for the 13 A fuse (Table 41.3 of BS 7671 gives maximum Zs values for BS 1362 fuses), not just for the ring's 32 A device.
Pricing an FCU job in 2026
| Job | Typical price including materials |
|---|---|
| Switched FCU added to an existing ring, surface or chased, with certificate | £90–£160 |
| FCU with flex outlet for a boiler, new 3 A fuse, certificate | £100–£170 |
| Fused spur with three new sockets | £220–£380 |
| Fan isolator and FCU for a bathroom fan (fan extra) | £110–£190 |
| Moving an inaccessible cooker hood FCU above the worktop | £120–£200 |
Chasing and making good are the variable; a surface-mounted FCU in a garage is an hour, a flush FCU in a finished kitchen with tiles is half a day.
Frequently Asked Questions
Can I put two sockets on an unfused spur?
No. BS 7671 Appendix 15 limits an unfused spur to one single or one twin socket-outlet or one FCU. Fit an FCU with a 13 A fuse at the start of the spur and you can feed as many sockets as you like on the load side, with the cable sized to the fuse.
Does a fused spur need to be in 2.5 mm²?
Not necessarily. The cable from the ring to the FCU is 2.5 mm² because it is unprotected other than by the ring's device. The cable on the load side of the FCU only has to carry the fuse rating, so 1.5 mm² is acceptable behind a 13 A fuse for most installation methods, and 1.0 mm² behind a 3 A fuse. Check the current-carrying capacity for the installation method in Table 4D5 where the cable is in insulation.
Can I spur an immersion heater from the kitchen ring through an FCU?
No. An immersion heater is a 3 kW continuous load and Appendix 15 says it, and any load over 2 kW, should be on a dedicated circuit. The same applies to electric showers and instantaneous water heaters. A towel rail at 300–600 W is fine on an FCU.
Switched or unswitched FCU for a boiler?
Switched, double-pole, usually with a neon, fitted next to the boiler and reachable. The switch is the local isolation for servicing. Some gas engineers prefer an unswitched FCU plus a separate double-pole isolator; either satisfies Regulation 537.3 as long as there is an accessible double-pole switch.
Is adding an FCU notifiable under Part P?
Not in England, unless it is in a bathroom zone or part of a new circuit. It still needs a Minor Electrical Installation Works Certificate. In Wales the scope of notifiable work is wider; check Approved Document P (Wales) for kitchen work.
Regulations & Standards
BS 7671:2018+A4:2026 — Requirements for Electrical Installations: Regulation 411.3.3 (RCD protection for socket-outlets), 433.1.204 (ring final circuits), 522.6.202 (cables concealed in walls), 537.3 (switching off for mechanical maintenance), Section 701 (bathrooms), Table 41.3 (maximum Zs for BS 1362 fuses), Appendix 15 (ring and radial final circuit arrangements)
BS 1363-4:2016+A1:2018 — 13 A plugs, socket-outlets, adaptors and connection units: Part 4, 13 A fused connection units switched and unswitched
BS 1362:1973 — General purpose fuse links for domestic and similar purposes
BS EN 61558-2-5 — Shaver supply units for bathrooms
Building Regulations 2010, Approved Document P (Electrical safety — dwellings), England 2013 edition and Wales edition
Building Regulations 2010, Approved Document M, Volume 1 (Dwellings) — heights of switches and controls
IET On-Site Guide (BS 7671:2018+A4:2026 edition) — standard circuit arrangements and spur limits
IET Guidance Note 1: Selection and Erection
GOV.UK — Approved Document M: Access to and use of buildings
spurring off a socket rules — the one-socket rule for unfused spurs in detail
ring final circuit explained — how a 32 A device protects a 2.5 mm² ring
spur vs radial vs ring final — choosing the circuit arrangement
electrical certificates eic mwc eicr explained — minor works certification for a new spur
bathroom fan wiring — 3-pole isolation for timer fans
cooker circuits — why cookers over 2 kW get a dedicated circuit