Emergency Lighting: BS 5266 Requirements, Testing Schedules & Log Books

Quick Answer: Emergency lighting in commercial and public buildings must comply with BS 5266-1:2016. It must provide a minimum 1 lux at floor level along escape routes and 5 lux at high-risk task areas, with a minimum 1-hour duration for escape lighting and 3-hour duration for high-risk areas. Monthly function tests and annual full-duration tests are required, all logged in a maintenance record.

Summary

Emergency lighting is legally required in all commercial premises, public buildings, and places of assembly. Its purpose is to illuminate escape routes and exit signs when the main power supply fails, allowing occupants to evacuate safely. Unlike routine lighting maintenance, emergency lighting has mandatory test schedules and log book requirements set out in BS 5266-1:2016 (the UK's main emergency lighting standard) and supported by the Regulatory Reform (Fire Safety) Order 2005.

For electricians and building services contractors, emergency lighting is a specialised area with clear compliance obligations. The person responsible for the premises (the "responsible person" under the Fire Safety Order) must ensure the system is maintained, tested, and documented. In practice, this means contracted maintenance visits with written test reports. A premises that cannot produce a complete maintenance log when inspected by the fire authority may face enforcement action even if the lights themselves are functioning.

Emergency lighting is distinct from exit signs (which may or may not be illuminated by emergency circuits) and fire alarm systems (covered by BS 5839). However, the systems must work together — power failure activating the fire alarm should simultaneously activate emergency lighting where required.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Emergency Lighting Type When Lights Are On Application
Non-maintained Only during power failure Offices, retail, factories
Maintained Continuously (normal + emergency mode) Cinemas, theatres, areas with blackout
Sustained Main source on normally; emergency source on failure Mixed use areas
Combined Normal luminaire + emergency module Cost-effective retrofit
Area Type Minimum Illuminance Duration
Escape route (covered) 1 lux (centre line) 1 hour minimum
Escape route (open area) 0.5 lux 1 hour minimum
High-risk task area 15 lux or 10% normal 3 hours
Anti-panic (open area >60m²) 0.5 lux 1 hour
Safety signage 1 hour minimum
Stairwells, changes of direction 1 lux at floor 1 hour
Test Type Frequency Duration Action If Failure
Function test Monthly Brief (activate, verify) Record fault; repair promptly
Full duration test Annual Full rated duration Record fault; repair promptly
Lamp check During function test Replace failed lamps
Battery check Annual Full duration run Replace batteries if below spec

Detailed Guidance

BS 5266 Zone Requirements

BS 5266-1:2016 requires emergency lighting in specific locations:

Mandatory locations:

Spacing and positioning:

Self-Contained vs Central Battery Systems

Self-contained fittings:

Central battery systems:

Addressable/networked systems:

Test Schedules and Log Books

BS 5266 prescribes specific testing:

Monthly function test:

  1. Simulate a supply failure (switch off normal power supply to emergency circuit or use test facility)
  2. Verify all luminaires and exit signs illuminate
  3. Allow sufficient time to confirm operation (typically 1-3 minutes for a basic check)
  4. Restore normal supply
  5. Record in log book: date, result, any faults found, initials of person testing

Annual full duration test:

  1. Simulate supply failure at the start of the working day (so fittings can recharge by end of day)
  2. Allow emergency lights to operate for their full rated duration (1 or 3 hours)
  3. Record illuminance levels where possible (lux meter measurements)
  4. Restore normal supply; verify all fittings return to charge mode
  5. Record in log book: date, duration, results, faults, person carrying out test

Log book requirements: The log book must include:

Recommended log books are available from ICEL (Industry Committee for Emergency Lighting) and fire protection suppliers.

Certificate of Design, Installation, and Commissioning

When an emergency lighting system is installed or significantly modified, a certificate should be issued in accordance with BS 5266-1 Annex A. This covers:

This certificate is passed to the building owner/occupier and should be kept with the system log book.

Emergency Lighting in Dwellings

BS 5266 primarily applies to commercial and public premises. For domestic properties:

Frequently Asked Questions

Who is responsible for maintaining emergency lighting?

The "responsible person" under the Regulatory Reform (Fire Safety) Order 2005 — typically the building owner or employer. They may appoint a competent contractor to carry out the maintenance, but the legal responsibility remains with the responsible person. Failure to maintain the system and keep records can result in prosecution.

How long do emergency lighting batteries last?

Self-contained emergency light batteries typically last 3-5 years. After this, capacity drops and the fitting may fail the full duration test. Battery replacement (rather than whole-fitting replacement) is usually possible and more cost-effective. Central battery systems use larger sealed lead-acid or NiCd batteries with 5-10 year life. Check manufacturer specifications and replace on a planned maintenance basis rather than waiting for failures.

Does emergency lighting need a dedicated circuit?

Self-contained fittings don't need a dedicated circuit — they operate independently on failure of the normal supply. However, the normal charging supply to each fitting must be maintained continuously (it charges the battery). Central battery systems require a dedicated final circuit to each zone, permanently live to allow charging.

Can I just use combined luminaires to save money?

Combined luminaires (a standard fitting with an added emergency module) are a cost-effective solution for retrofit or lower-specification areas. They are acceptable under BS 5266 provided the emergency module meets the required duration and illuminance. The limitation is that they're generally maintained non-maintained units — they only illuminate in emergency mode, which means the area goes dark (from the combined unit) then comes back dimly. Where continuous illumination is required (cinemas, theatres), maintained-mode dedicated emergency fittings are needed.

Regulations & Standards