Summary
Downlights are the default ceiling fitting in kitchens, bathrooms and, increasingly, every other room, and most of the complaints about them are layout complaints: too many in a grid that lights the floor and leaves the worktop in shadow; too few so the room is gloomy with dark corners; scallops of light on the walls where the outer row is too close; one fitting dead-centre over the island that lights the top of the cook's head. The electrician is usually the one who decides where the holes go, often on the morning of the job, so a method that gets it right first time is worth having.
The two tools are a spacing rule of thumb and the lumen method. The rule of thumb gets the fittings evenly distributed with no scalloping and no dark edges; the lumen method checks that there are enough of them, or more often that there are not too many. Both are then adjusted for the room's real geometry: where the joists run, where the worktops, bath, mirror, bed and sofa are, where the ceiling changes height, where the extractor, smoke alarm and loft hatch already are. A plan drawn on paper (or the ceiling) before any holes are cut saves the patching that a wrongly placed cut-out costs.
This guide gives the rules, the calculation with worked examples for the common rooms, the room-by-room placement advice that stops the usual mistakes, and the compliance points that follow: fire rating, insulation clearance, bathroom zones, Part L efficacy and Part P. For fire-rated fittings see fire rated downlights explained; for lamp and driver choice see led vs halogen downlights; for the broader design picture see lighting design; for pricing see downlight installation pricing guide.
Key Facts
- Spacing rule — distance between fittings ≈ ceiling height ÷ 2 for 36–40° beam fittings used for general lighting; wider 60° beams allow up to ceiling height × 0.6–0.7; narrow 24° accent beams need closer spacing or should not be used for general light at all.
- Wall distance — the outer row at half the fitting spacing from the wall (so about 0.5–0.6 m on a 2.4 m ceiling). Closer than about 0.4 m produces bright scallops on the wall; further than 0.75 m leaves the perimeter dark.
- Worktop rule — over a run of kitchen units, set the fittings 300–450 mm out from the wall face (so roughly at the front edge of the 600 mm worktop) and about 1 m apart along it, so the light falls on the worktop in front of the person standing at it rather than on their head and shoulders casting a shadow.
- Target illuminance (CIBSE SLL Code for Lighting / LG9) — kitchen worktop 300 lux (150–200 lux general); living room 150–200 lux general with task lighting for reading; bedroom 100–150 lux; bathroom 150 lux (200–300 at the mirror); hall, stairs and landing 100 lux; home office 300–500 lux at the desk; utility 200 lux.
- Lumen method — N = (E × A) ÷ (F × UF × MF), where E is the target lux, A the floor area in m², F the lumens per fitting (luminaire output, not the bare lamp), UF the utilisation factor (0.5–0.7 for downlights in a domestic room with light walls and ceiling, lower for dark decor) and MF the maintenance factor (0.8 for LED in a clean domestic environment).
- Typical outputs — integrated LED downlights: 5–6 W around 400–550 lm; 7–9 W around 650–850 lm; 10–13 W around 900–1,200 lm. GU10 lamps: 4–5 W around 350–450 lm; 6–7 W around 500–650 lm. Use the luminaire output figure from the data sheet, which includes losses in the bezel and diffuser.
- Efficacy (Approved Document L Volume 1, 2021) — fixed lighting in new dwellings and in extensions must achieve at least 75 lamp-lumens per circuit-watt; most LED downlights achieve 80–120 lm/W. Halogen does not comply.
- Cut-out sizes — most LED downlights need a 65–75 mm hole (common sizes 68, 70, 72 and 74 mm); check the fitting before buying the hole saw. Joists at 400 mm centres with 47 mm timber leave a 353 mm clear bay, so a fitting cannot sit on the joist line and the grid must be shifted to miss them.
- Joist and insulation clearance — manufacturer's instructions govern; typical requirements are at least 50 mm from timber for non-fire-rated fittings, and for fire-rated fittings the specific tested clearances. Many current fire-rated LED downlights are rated for insulation to abut or cover; those that are not need an insulation guard or hood.
- Fire rating — where the ceiling is part of a fire-resisting floor (every floor in a house of three or more storeys, loft conversions, flats, rooms over integral garages), the fittings must be fire-rated for the ceiling's rating (30, 60 or 90 minutes) and the tested ceiling build-up, under Approved Document B Volume 1. A fire-rated fitting in a single-storey ceiling with a loft above is not required but is the usual default.
- Acoustic and thermal — in separating floors between flats, downlights must not compromise the Part E acoustic performance; use acoustic-rated fittings or hoods. Holes in an insulated ceiling under a cold loft lose heat and allow moist air into the loft; sealed (IP-rated or "air-tight") fittings help.
- Bathroom zones — a downlight in Zone 1 (above the bath or shower up to 2.25 m) must be at least IPX4 (IP44 is typical) and the circuit 30 mA RCD protected; most bathroom ceilings at 2.4 m are above Zone 1 and outside the zones, where IP rating is not required but IP44 or better is sensible for condensation. Fittings in Zone 1 should be SELV or 230 V with RCD, and never openable without a tool.
- Dimming — LED downlights need a trailing-edge or LED-compatible dimmer with a minimum load within the dimmer's range and the fitting marked as dimmable; mixing fittings from different batches on one dimmer causes flicker and uneven dimming.
- Colour temperature and CRI — 2700 K (warm) for living rooms and bedrooms, 3000 K for kitchens and bathrooms, 4000 K only for utility and task areas; CRI 80 minimum, 90 for kitchens where food colour matters. Use the same colour temperature throughout a room.
- Glare — a downlight viewed from below at a shallow angle is uncomfortable; recessed (deep-set) fittings with a baffle cut glare, and fittings should not be placed directly above where people sit or lie (over the sofa, over the bed, directly over the bath).
- Circuit loading — LED downlights draw little (a room of 10 at 8 W is 80 W), so the limit is usually the number of points and the dimmer rating rather than the circuit; a 6 A lighting circuit is adequate for several rooms of LED downlights, but check the total against BS 7671 and the dimmer's maximum load.
- Part P — adding downlights to an existing lighting circuit is not notifiable in England, including in a bathroom, unless a new circuit is installed or the consumer unit is changed; in Wales, additions in a bathroom remain notifiable.
- Cost — supply and fit of fire-rated integrated LED downlights into an existing ceiling from above (loft access): £35–£60 each including the fitting; without access from above, cutting in and fishing cable: £50–£90 each; a typical 12-fitting kitchen on a new switch drop: £500–£900; dimmer upgrade £40–£80.
Quick Reference Table
Quoting an electrical job? Describe the work and squote handles the pricing.
Try squote free →| Room | Floor area | Target lux | Fitting (lumens) | Fittings needed (UF 0.6, MF 0.8) | Suggested grid |
|---|---|---|---|---|---|
| Kitchen (galley) | 3.0 × 2.4 m = 7.2 m² | 300 | 750 lm | 6 | 2 rows × 3, rows over worktop edges |
| Kitchen (family) | 4.0 × 3.5 m = 14 m² | 300 | 750 lm | 12 | 3 rows × 4, outer rows at 450 mm from wall units |
| Kitchen-diner | 6.0 × 4.0 m = 24 m² | 300 kitchen / 200 dining | 750 lm | 12 kitchen end + 6 dining end | Two switched/dimmed groups |
| Living room | 5.0 × 4.0 m = 20 m² | 150 | 700 lm | 9 | 3 × 3 at 1.2–1.3 m, dimmed; add lamps for task |
| Bedroom (double) | 4.0 × 3.5 m = 14 m² | 100–150 | 600 lm | 5–6 | 2 × 3 avoiding directly over the bed |
| Bathroom | 2.5 × 2.0 m = 5 m² | 150 (300 at mirror) | 600 lm | 3–4 | Triangle or 2 × 2, one near mirror, IP44 |
| En-suite / shower room | 2.0 × 1.5 m = 3 m² | 150 | 500 lm | 2 | One over the dry area, one near basin; IP44/IP65 |
| Hallway | 4.0 × 1.2 m = 4.8 m² | 100 | 600 lm | 2 | Single row at 1.5–2 m centres |
| Landing | 3.0 × 1.0 m = 3 m² | 100 | 600 lm | 1–2 | Avoid directly over the stair nosing |
| Home office | 3.5 × 3.0 m = 10.5 m² | 300 | 750 lm | 9 | 3 × 3; one row over the desk, no screen glare |
| Utility | 2.5 × 2.0 m = 5 m² | 200 | 750 lm | 3 | Row over the worktop/appliances, 4000 K acceptable |
Detailed Guidance
Step 1: the spacing rule
Start with the ceiling height. For a 2.4 m ceiling and a standard 36–40° beam, the useful pool of light at worktop or table height is about 1.2–1.4 m across, so fittings at 1.2 m centres overlap slightly and give even coverage. For a 2.7 m ceiling use 1.3–1.4 m; for a 3 m ceiling 1.5 m. Then set the outer row at half the spacing from the wall, 0.6 m on a 2.4 m ceiling. Divide the room's length and width by the spacing and round to the nearest whole number of bays; that gives rows and columns. A 4.0 × 3.5 m room at 1.2 m spacing: 4.0 ÷ 1.2 = 3.3 bays → 3 bays across (fittings at 0.67 m from each end and 1.33 m apart); 3.5 ÷ 1.2 = 2.9 → 3 bays (0.58 m from each side, 1.17 m apart). That is a 3 × 3 grid of 9 fittings, evenly distributed.
Step 2: the lumen method check
Then check the quantity against the illuminance target. Taking the same 4.0 × 3.5 m room as a kitchen (300 lux) with 750 lm fittings:
N = (300 × 14) ÷ (750 × 0.6 × 0.8) = 4,200 ÷ 360 = 11.7, so 12 fittings.
The spacing rule gave 9; the lumen method says 12 for a kitchen. The answer is to tighten the grid to 3 rows × 4 (1.0 m along, 1.17 m across), or to accept 9 general fittings and add under-cabinet task lighting to lift the worktop to 300 lux, which is usually the better design because it puts the light where the task is and lets the general lighting dim.
The same room as a bedroom at 150 lux with 600 lm fittings: N = (150 × 14) ÷ (600 × 0.6 × 0.8) = 2,100 ÷ 288 = 7.3, so 7–8 fittings; a 2 × 3 grid of 6 plus bedside lamps is the usual compromise, with the fittings dimmed. The lesson of the calculation is that living rooms and bedrooms are routinely over-lit by a kitchen-style grid; nine 800 lm fittings in a 20 m² living room gives 230 lux at full output, which is why they are always dimmed to a quarter.
Utilisation factor depends on the room: 0.65–0.7 for a small room with white walls and ceiling, 0.5–0.55 for a large room with dark walls or a dark floor, lower still with exposed dark beams. Maintenance factor of 0.8 reflects LED lumen depreciation and dust over the installation's life.
Step 3: adjust for the room
The grid is a starting point. Move fittings to work with the room:
- Kitchens. Put the rows over the worktop front edges, 300–450 mm out from the wall units, so the light falls on the work surface in front of the cook. Over an island or peninsula, two or three fittings along its length at the quarter points, not one in the centre. Do not put a fitting where the extractor hood or its ducting will be; most hoods have their own lamps. Avoid a fitting directly above the hob if the hood is a ceiling type.
- Bathrooms. One fitting near the basin to light the face at the mirror (ideally paired with mirror lighting, since a downlight alone casts shadows under the brow and chin), the rest to light the dry area and the shower. Over a bath or shower in Zone 1, IP44 minimum and RCD protected; many installers use IP65 throughout to resist steam. Keep the extractor fan in a usable position and not in a fitting's spot.
- Living rooms and bedrooms. Light the perimeter and the walls, not the centre of the floor and not the seating; a fitting directly over the sofa or bed shines into eyes. Pull the grid towards the walls, dim everything, and expect table and floor lamps to do the task lighting. Wall-washing fittings (angled or asymmetric) along a feature wall are often better than a centre grid.
- Halls and landings. A single row at 1.5–2 m centres; on landings avoid a fitting over the stair nosing where a shadow falls on the step, and remember the smoke alarm needs its own clear position (300 mm from any light fitting under BS 5839-6:2019).
- Sloping ceilings. Downlights in a sloping ceiling throw light sideways; use gimbal (tilt) fittings angled to the vertical, and increase the quantity on the high side.
- Changes of ceiling height, beams and bulkheads. Treat each ceiling area as its own zone and lay out separately; a bulkhead over the units often takes a row of its own.
Step 4: find the joists before you mark the ceiling
Nothing wastes more time than marking a perfect grid and finding every third fitting lands on a joist. From the loft or the floor above, or with a joist detector, mark the joist centres on the ceiling with masking tape before laying out. Joists at 400 mm centres leave about 350 mm clear between them; at 600 mm centres about 550 mm. Shift the whole grid, not individual fittings, so the pattern stays regular, or rotate it to run the rows parallel to the joists. Keep each cut-out at least 50 mm from a joist face (or the manufacturer's figure), and check for noggins, cables, pipes and the cold-water tank above before cutting. Cut with a hole saw of the exact cut-out size with a dust shroud or a vacuum held under it; an oversized hole shows round the bezel and an undersized one cracks the plaster when the clips go in.
Step 5: compliance points
- Fire. Determine whether the ceiling is a fire-separating element. In a two-storey house, the first-floor ceiling under a loft is not (fire-rated fittings are good practice, not a requirement); the ground-floor ceiling under the first floor is a 30-minute floor in modern construction and in loft-converted houses, and all floors in a three-storey house are. Flats require 60 minutes between dwellings. The fitting's fire rating must be from a test on the same ceiling build-up (board type and thickness, joist spacing); see fire rated downlights explained.
- Insulation and airtightness. Under Approved Document L, a hole in an insulated ceiling is a thermal bypass; use fittings rated for insulation contact so the quilt can stay continuous, or fit loft hoods. Sealed fittings also stop warm moist air reaching the cold loft, a common cause of condensation on the underside of the roof.
- Acoustics. In separating floors between flats (Part E), downlights need acoustic hoods or acoustic-rated fittings to maintain the tested performance.
- Efficacy. New dwellings and extensions: 75 lamp-lumens per circuit-watt minimum for fixed lighting under Approved Document L Volume 1 (2021). Any LED downlight meets it; retrofits in existing rooms are not controlled, but there is no reason to fit anything else.
- Bathroom zones. Zone 1 fittings IPX4 minimum and RCD protected; outside the zones no IP requirement but IP44 is sensible. SELV fittings in Zone 1 need the transformer outside the zones. See bathroom zones and ip ratings.
- Circuit design. Adding points to an existing lighting circuit is a Minor Works job with the usual tests (continuity, IR, polarity, Zs, RCD). Where the circuit has no 30 mA RCD and the cables will be concealed in the ceiling at less than 50 mm depth, BS 7671:2018+A4:2026 Regulation 522.6.202 requires RCD protection or earthed mechanical protection for the new cables; in practice fit an RCBO.
- Part P. Not notifiable in England unless a new circuit is run or the consumer unit changed; notifiable in Wales for work in a bathroom. Issue a Minor Electrical Installation Works Certificate for additions to an existing circuit.
Controls
Group fittings into switched or dimmed circuits by function, not by position: kitchen worktop row separately from the dining-end fittings; bathroom general separately from the mirror; living room perimeter separately from any accent fittings. A trailing-edge LED dimmer per group, with the fittings all from one batch and marked dimmable, avoids the flicker and drop-out that follow mixed fittings on a leading-edge dimmer. For smart control, choose fittings and drivers that are compatible with the chosen protocol rather than adding a smart dimmer to fittings that were never designed to dim. See lighting controls.
Frequently Asked Questions
How many downlights do I need in a kitchen?
Work it out from the area and a 300 lux target: with 750 lm fittings and a utilisation factor of 0.6 and maintenance factor of 0.8, you need about 0.83 fittings per square metre, so a 12 m² kitchen needs 10 and a 16 m² kitchen 13. In practice a 1 m grid over the working area with the rows aligned to the worktop edges, plus under-cabinet task lighting, gives a better result with fewer ceiling fittings than a dense grid that lights the floor.
How far from the wall should the first row of downlights be?
Half the spacing between fittings, so about 0.5–0.6 m on a 2.4 m ceiling. Closer and the wall shows bright scallops where each beam hits it; further and the perimeter of the room is dark. In a kitchen the rule changes: the row along the units goes 300–450 mm from the wall face, so the light lands on the worktop and not on the back of the cook's head.
Can I put downlights anywhere in a bathroom?
Anywhere above the zones (over 2.25 m above the floor outside the bath or shower footprint) without an IP requirement, though IP44 is sensible for steam. Directly above the bath or shower up to 2.25 m is Zone 1 and the fitting must be at least IPX4 and on a 30 mA RCD; most people use IP65 there. Keep the extractor fan's position in mind and put one fitting near the mirror. A ceiling under 2.25 m puts the fittings over the bath or shower into Zone 1 and often into Zone 0 (inside the bath), which rules out 230 V fittings altogether.
Do all downlights have to be fire-rated?
Only where the ceiling is part of a fire-resisting floor: between a ground floor and a first floor in modern construction, every floor in a three-storey house or a house with a loft conversion, between flats, and over an integral garage. A first-floor ceiling under an unconverted loft is not a fire-separating element. Fire-rated fittings are nonetheless the default most installers fit everywhere, because they are only marginally dearer, they restore the ceiling's integrity, and they avoid the argument with Building Control.
Why do the downlights flicker or not dim down fully?
The dimmer is the wrong type or the fittings are mismatched. LED downlights need a trailing-edge dimmer rated for LED with a minimum load lower than the total installed wattage (ten 8 W fittings are 80 W, below the minimum of many older dimmers), and every fitting on the dimmer should be the same make, model and batch. Non-dimmable fittings on any dimmer flicker and fail early. Check the fitting is marked dimmable and the dimmer's compatibility list.
Regulations & Standards
Building Regulations 2010, Approved Document L Volume 1: Dwellings (2021 edition incorporating 2023 amendments) — fixed lighting efficacy of 75 lamp-lumens per circuit-watt; thermal performance of ceilings.
Approved Document B Volume 1: Dwellings (2019 edition incorporating 2020 and 2022 amendments) — fire resistance of floors; recessed fittings in fire-separating ceilings.
Approved Document E (2003 edition incorporating 2004, 2010, 2013 and 2015 amendments) — resistance to the passage of sound; penetrations through separating floors.
Approved Document P (2013 edition) — electrical safety in dwellings; notifiability.
BS 7671:2018+A4:2026 — Section 701 (bathroom zones and IP ratings), Regulation 522.6.202 (concealed cables in walls and partitions), Chapter 55 (luminaires), Section 559.
BS EN 60598-1:2021 — Luminaires: general requirements and tests.
BS EN 60598-2-2:2012 — Luminaires: particular requirements for recessed luminaires.
BS 5839-6:2019+A1:2020 — Fire detection and alarm systems for dwellings; smoke alarm siting relative to light fittings.
CIBSE SLL Code for Lighting (2022) — illuminance recommendations by task and space.
CIBSE SLL Lighting Guide LG9: Lighting for communal residential buildings — domestic lighting guidance.
BS EN 12464-1:2021 — Light and lighting: lighting of indoor work places (home office and task areas).
Approved Document L, Volume 1: Dwellings — GOV.UK — lighting efficacy requirement.
Approved Document B, Volume 1: Dwellings — GOV.UK — fire resistance of floors and recessed fittings.
CIBSE Society of Light and Lighting — Code for Lighting and Lighting Guides — illuminance targets.
IET — BS 7671 Wiring Regulations — bathroom zones and cable protection.
LIA — Lighting Industry Association technical guidance — luminaire performance and compliance.
BRE — Lighting in homes guidance — domestic lighting design research.
fire rated downlights explained — when a fire rating is required and how to read the test certificate.
led vs halogen downlights — lamp types, drivers, colour temperature and efficacy.
lighting design — circuits, controls and whole-house lighting design.
lighting controls — dimmers, smart control and switching groups.