Summary

Downlights are the default ceiling fitting in kitchens, bathrooms and, increasingly, every other room, and most of the complaints about them are layout complaints: too many in a grid that lights the floor and leaves the worktop in shadow; too few so the room is gloomy with dark corners; scallops of light on the walls where the outer row is too close; one fitting dead-centre over the island that lights the top of the cook's head. The electrician is usually the one who decides where the holes go, often on the morning of the job, so a method that gets it right first time is worth having.

The two tools are a spacing rule of thumb and the lumen method. The rule of thumb gets the fittings evenly distributed with no scalloping and no dark edges; the lumen method checks that there are enough of them, or more often that there are not too many. Both are then adjusted for the room's real geometry: where the joists run, where the worktops, bath, mirror, bed and sofa are, where the ceiling changes height, where the extractor, smoke alarm and loft hatch already are. A plan drawn on paper (or the ceiling) before any holes are cut saves the patching that a wrongly placed cut-out costs.

This guide gives the rules, the calculation with worked examples for the common rooms, the room-by-room placement advice that stops the usual mistakes, and the compliance points that follow: fire rating, insulation clearance, bathroom zones, Part L efficacy and Part P. For fire-rated fittings see fire rated downlights explained; for lamp and driver choice see led vs halogen downlights; for the broader design picture see lighting design; for pricing see downlight installation pricing guide.

Key Facts

Quick Reference Table

Quoting an electrical job? Describe the work and squote handles the pricing.

Try squote free →
Room Floor area Target lux Fitting (lumens) Fittings needed (UF 0.6, MF 0.8) Suggested grid
Kitchen (galley) 3.0 × 2.4 m = 7.2 m² 300 750 lm 6 2 rows × 3, rows over worktop edges
Kitchen (family) 4.0 × 3.5 m = 14 m² 300 750 lm 12 3 rows × 4, outer rows at 450 mm from wall units
Kitchen-diner 6.0 × 4.0 m = 24 m² 300 kitchen / 200 dining 750 lm 12 kitchen end + 6 dining end Two switched/dimmed groups
Living room 5.0 × 4.0 m = 20 m² 150 700 lm 9 3 × 3 at 1.2–1.3 m, dimmed; add lamps for task
Bedroom (double) 4.0 × 3.5 m = 14 m² 100–150 600 lm 5–6 2 × 3 avoiding directly over the bed
Bathroom 2.5 × 2.0 m = 5 m² 150 (300 at mirror) 600 lm 3–4 Triangle or 2 × 2, one near mirror, IP44
En-suite / shower room 2.0 × 1.5 m = 3 m² 150 500 lm 2 One over the dry area, one near basin; IP44/IP65
Hallway 4.0 × 1.2 m = 4.8 m² 100 600 lm 2 Single row at 1.5–2 m centres
Landing 3.0 × 1.0 m = 3 m² 100 600 lm 1–2 Avoid directly over the stair nosing
Home office 3.5 × 3.0 m = 10.5 m² 300 750 lm 9 3 × 3; one row over the desk, no screen glare
Utility 2.5 × 2.0 m = 5 m² 200 750 lm 3 Row over the worktop/appliances, 4000 K acceptable

Detailed Guidance

Step 1: the spacing rule

Start with the ceiling height. For a 2.4 m ceiling and a standard 36–40° beam, the useful pool of light at worktop or table height is about 1.2–1.4 m across, so fittings at 1.2 m centres overlap slightly and give even coverage. For a 2.7 m ceiling use 1.3–1.4 m; for a 3 m ceiling 1.5 m. Then set the outer row at half the spacing from the wall, 0.6 m on a 2.4 m ceiling. Divide the room's length and width by the spacing and round to the nearest whole number of bays; that gives rows and columns. A 4.0 × 3.5 m room at 1.2 m spacing: 4.0 ÷ 1.2 = 3.3 bays → 3 bays across (fittings at 0.67 m from each end and 1.33 m apart); 3.5 ÷ 1.2 = 2.9 → 3 bays (0.58 m from each side, 1.17 m apart). That is a 3 × 3 grid of 9 fittings, evenly distributed.

Step 2: the lumen method check

Then check the quantity against the illuminance target. Taking the same 4.0 × 3.5 m room as a kitchen (300 lux) with 750 lm fittings:

N = (300 × 14) ÷ (750 × 0.6 × 0.8) = 4,200 ÷ 360 = 11.7, so 12 fittings.

The spacing rule gave 9; the lumen method says 12 for a kitchen. The answer is to tighten the grid to 3 rows × 4 (1.0 m along, 1.17 m across), or to accept 9 general fittings and add under-cabinet task lighting to lift the worktop to 300 lux, which is usually the better design because it puts the light where the task is and lets the general lighting dim.

The same room as a bedroom at 150 lux with 600 lm fittings: N = (150 × 14) ÷ (600 × 0.6 × 0.8) = 2,100 ÷ 288 = 7.3, so 7–8 fittings; a 2 × 3 grid of 6 plus bedside lamps is the usual compromise, with the fittings dimmed. The lesson of the calculation is that living rooms and bedrooms are routinely over-lit by a kitchen-style grid; nine 800 lm fittings in a 20 m² living room gives 230 lux at full output, which is why they are always dimmed to a quarter.

Utilisation factor depends on the room: 0.65–0.7 for a small room with white walls and ceiling, 0.5–0.55 for a large room with dark walls or a dark floor, lower still with exposed dark beams. Maintenance factor of 0.8 reflects LED lumen depreciation and dust over the installation's life.

Step 3: adjust for the room

The grid is a starting point. Move fittings to work with the room:

Step 4: find the joists before you mark the ceiling

Nothing wastes more time than marking a perfect grid and finding every third fitting lands on a joist. From the loft or the floor above, or with a joist detector, mark the joist centres on the ceiling with masking tape before laying out. Joists at 400 mm centres leave about 350 mm clear between them; at 600 mm centres about 550 mm. Shift the whole grid, not individual fittings, so the pattern stays regular, or rotate it to run the rows parallel to the joists. Keep each cut-out at least 50 mm from a joist face (or the manufacturer's figure), and check for noggins, cables, pipes and the cold-water tank above before cutting. Cut with a hole saw of the exact cut-out size with a dust shroud or a vacuum held under it; an oversized hole shows round the bezel and an undersized one cracks the plaster when the clips go in.

Step 5: compliance points

Controls

Group fittings into switched or dimmed circuits by function, not by position: kitchen worktop row separately from the dining-end fittings; bathroom general separately from the mirror; living room perimeter separately from any accent fittings. A trailing-edge LED dimmer per group, with the fittings all from one batch and marked dimmable, avoids the flicker and drop-out that follow mixed fittings on a leading-edge dimmer. For smart control, choose fittings and drivers that are compatible with the chosen protocol rather than adding a smart dimmer to fittings that were never designed to dim. See lighting controls.

Frequently Asked Questions

How many downlights do I need in a kitchen?

Work it out from the area and a 300 lux target: with 750 lm fittings and a utilisation factor of 0.6 and maintenance factor of 0.8, you need about 0.83 fittings per square metre, so a 12 m² kitchen needs 10 and a 16 m² kitchen 13. In practice a 1 m grid over the working area with the rows aligned to the worktop edges, plus under-cabinet task lighting, gives a better result with fewer ceiling fittings than a dense grid that lights the floor.

How far from the wall should the first row of downlights be?

Half the spacing between fittings, so about 0.5–0.6 m on a 2.4 m ceiling. Closer and the wall shows bright scallops where each beam hits it; further and the perimeter of the room is dark. In a kitchen the rule changes: the row along the units goes 300–450 mm from the wall face, so the light lands on the worktop and not on the back of the cook's head.

Can I put downlights anywhere in a bathroom?

Anywhere above the zones (over 2.25 m above the floor outside the bath or shower footprint) without an IP requirement, though IP44 is sensible for steam. Directly above the bath or shower up to 2.25 m is Zone 1 and the fitting must be at least IPX4 and on a 30 mA RCD; most people use IP65 there. Keep the extractor fan's position in mind and put one fitting near the mirror. A ceiling under 2.25 m puts the fittings over the bath or shower into Zone 1 and often into Zone 0 (inside the bath), which rules out 230 V fittings altogether.

Do all downlights have to be fire-rated?

Only where the ceiling is part of a fire-resisting floor: between a ground floor and a first floor in modern construction, every floor in a three-storey house or a house with a loft conversion, between flats, and over an integral garage. A first-floor ceiling under an unconverted loft is not a fire-separating element. Fire-rated fittings are nonetheless the default most installers fit everywhere, because they are only marginally dearer, they restore the ceiling's integrity, and they avoid the argument with Building Control.

Why do the downlights flicker or not dim down fully?

The dimmer is the wrong type or the fittings are mismatched. LED downlights need a trailing-edge dimmer rated for LED with a minimum load lower than the total installed wattage (ten 8 W fittings are 80 W, below the minimum of many older dimmers), and every fitting on the dimmer should be the same make, model and batch. Non-dimmable fittings on any dimmer flicker and fail early. Check the fitting is marked dimmable and the dimmer's compatibility list.

Regulations & Standards